Safe Snap Barrier Z828

Zener Barrier 1 -channel, DC version, negative polarity, working voltage 26.5V at 10 mA, series resistance max. 327?, fuse rating 50mA, DIN rail mounting, number of channels: 1-channel type: DC, negative, working voltage: max. 27V, 26.5V at 10 mA.

Maker : Pepperl+Fuchs
Type : Z828
Part No : 71789

Category:

Description

The Zener Barrier prevents the transfer of unacceptably high energy from the safe area into the hazardous area. The zener diodes in the Zener Barrier are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation. If this voltage is exceeded, due to a fault in the safe area, the diodes start to conduct, causing the fuse to blow. The Zener Barrier has a negative polarity, i. e. the cathodes of the zener diodes are grounded.

Features

  • 1-channel
  • DCversion,negativepolarity
  • Workingvoltage26.5Vat10μA
  • Series resistance max. 327 Ω
  • Fuserating50mA
  • DINrailmounting

Specificatons

General specifications
Type DC version, negative polarity
Electrical specifications
Nominal resistance 300 Ω
Series resistance max. 327 Ω
Fuse rating 50 mA
Hazardous area connection
Connection terminals 1, 2
Safe area connection
Connection terminals 7, 8
Working voltage max. 27 V , 26.5 V at 10 µA
Conformity
Degree of protection IEC 60529
Ambient conditions
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Storage temperature -25 … 70 °C (-13 … 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals , max. core cross-section 2 x 2.5 mm2
Mass approx. 150 g
Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EC-Type Examination Certificate BAS 01 ATEX 7005
Group, category, type of protection Ex-Hexagon II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Statement of conformity TÜV 99 ATEX 1484 X
Group, category, type of protection, temperature class Ex-Hexagon II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0118
UL approval
Control drawing 116-0139
CSA approval
Control drawing 116-0119
IECEx approval IECEx BAS 09.0142
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I